Discontinued - Relative pressure transmitter for liquids and gases

This product is discontinued

Relative pressure transmitter for measurement of liquids (also glycol-mixed) and gases (not ammonia).

Navigate on this page

Articles

(16 st)
  • TPL1 - Regin
    TPL1
    Output signal
    0…10 V DC
    Working range
    0…1 bar (0…100 kPa)
  • TPL1-420 - Regin
    TPL1-420
    Output signal
    4…20 mA
    Working range
    0…1 bar (0…100 kPa)
  • TPL2 - Regin
    TPL2
    Output signal
    0…10 V DC
    Working range
    0…2 bar (0…200 kPa)
  • TPL2-420 - Regin
    TPL2-420
    Output signal
    4…20 mA
    Working range
    0…2 bar (0…200 kPa)
  • TPL5 - Regin
    TPL5
    Output signal
    0…10 V DC
    Working range
    0…5 bar (0…500 kPa)
  • TPL5-420 - Regin
    TPL5-420
    Output signal
    4…20 mA
    Working range
    0…5 bar (0…500 kPa)
  • TPL10 - Regin
    TPL10
    Output signal
    0…10 V DC
    Working range
    0…10 bar (0…1000 kPa)
  • TPL10-420 - Regin
    TPL10-420
    Output signal
    4…20 mA
    Working range
    0…10 bar (0…1000 kPa)
  • TPL16 - Regin
    TPL16
    Output signal
    0…10 V DC
    Working range
    0…16 bar (0…1600 kPa)
  • TPL16-420 - Regin
    TPL16-420
    Output signal
    4…20 mA
    Working range
    0…16 bar (0…1600 kPa)
  • TPL25 - Regin
    TPL25
    Output signal
    0…10 V DC
    Working range
    0…25 bar (0…2500 kPa)
  • TPL25-420 - Regin
    TPL25-420
    Output signal
    4…20 mA
    Working range
    0…25 bar (0…2500 kPa)
  • TPL40 - Regin
    TPL40
    Output signal
    0…10 V DC
    Working range
    0…40 bar (0…4000 kPa)
  • TPL40-420 - Regin
    TPL40-420
    Output signal
    4…20 mA
    Working range
    0…40 bar (0…4000 kPa)
  • TPL100 - Regin
    TPL100
    Output signal
    0…10 V DC
    Working range
    0…100 bar (0…10000 kPa)
  • TPL100-420 - Regin
    TPL100-420
    Output signal
    4…20 mA
    Working range
    0…100 bar (0…10000 kPa)
Specifications for Discontinued - Relative pressure transmitter for liquids and gases
Supply voltage 24 V CA / 18…33 V DC ± 15% (output signal 0…10 V), 0.1 VA
11…33 V DC ± 15%, two-wire (output signal 4…20 mA), 0.5 VA
Output signal 0…10 V DC or 4…20 mA (two-wire)
Media temperature -15…+80°C
Accuracy ± 0.3 % es
Pressure connection R1/4"
Electrical connection DIN EN 175301 803-A
Packing EPDM
Dimensions Ø 40 x h 104mm
Protection class IP65
TPL105074

Heat sink to use the transmitter with liquid at a temperature aboc 80 °C (see datasheet)

ACCI10

Adapter 1/4" to 1/2"