TUTC1402 Duct humidity/temperature transmitter

Specifications

Specifications for TUTC1402
Dimensions, external (WxHxD) 75*103*266 mm
Tube length 23 cm
Tube diameter 12 mm
Insertion length 60…230 mm
Analogue output load impedance 4...20mA With power supply 11...17 V DC: RL <50 Ω
Relay With power supply 21...30 V DC: RL < 500 Ω
Measuring range, temp -20…50 °C
Output temperature NTC 10K-01 B3977
Measuring range, humidity 0…100 % RH
Output humidity 4-20 mA (2 wire)
Hysteresis, humidity ± 3% RH
Accuracy, gas in air 0.2
Colour, cover White
Colour, base White
Power supply (4...20 mA) Max 30 V DC, Min 11+(0.02xRL) V DC
Power consumption < 1 W
Specifications for Duct humidity/temperature transmitter
Appliance class Class III
Protection class IP65
Ambient humidity (non-condensing) 10…95 % RH
Ambient temp -5…50 °C
Storage temp -20…70 °C
Mounting Duct
Weight, incl. packaging 0.26 kg
Accuracy, temperature ± 1 K
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 0.75 mm²
Material, housing Polycarbonate

Accessories