TV09090U Immersion thermostats, IP 54

Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).

Specifications

Specifications for TV09090U
Sensor element Liquid-filled copper capillary with 120 mm brass pocket
Max. probe temperature 120 °C
Electrical contact SPDT microswitch
Dimensions, external (WxHxD) 88*70*132 mm
Setpoint-1 value, temperature min. 0 °C
Setpoint-1 value, temperature max. 90 °C
Setpoint value, temperature range 1 0...90 °C
Setpoint-2 value, temperature min. 0 °C
Setpoint-2 value, temperature max. 90 °C
Setpoint value, temperature range 2 0...90 °C
Hysteresis range 1, temperature 4±1 K
Hysteresis range 2, temperature 4±1 K
Breaking capacity range 1 NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
Breaking capacity range 2 NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
Specifications for Immersion thermostats, IP 54
Appliance class Class I
Protection class IP54
Ambient humidity (non-condensing) 10…90 % RH
Ambient temp -20…65 °C
Storage temp -20…70 °C
Storage humidity 10...95 % RH
Weight, incl. packaging 0.44 kg
Material, cover ABS
Material, base PC+ABS blend (Bayblend®)

Accessories