Room controllers for 2 or 4 pipe system, 0...10 V output
2- or 4-pipe fan coil control for room temperature.
Navigate on this page
Articles
(1 st)-
DB-TA-335-993
- 3 speeds
- -
- Change-over function, season
- Local S/W (4-pipe) neutral zone
- Sensor
- NT0220-NTC100
Specifications
Supply voltage | 24 V AC ± 10 %, 50/60 Hz |
---|---|
Load | Max. 6 A (speeds) |
Output | Proportional 0…10 V DC (R L > 10 kOhm) |
Power consumption | 1 W |
Sensor | NTC 100K |
Ambient temperature | 0…40°C |
Ambient humidity | 10…90 % RH (non-condensing) |
Setpoint | 5…30°C |
Hysteresis | 0.5 K |
Storage temperature | -20…+70°C |
Storage humidity | < 95% RH |
P-band | 1…5 K |
Neutral zone | 1…4K |
Casing | ABS fireproof according to UL94 V-0 color (RAL 9010) |
Weight | 210 g |
Dimensions | 144 x 82 x 34 mmmm |
Protection class | IP30 |
Isolation class | II |