Immersion thermostats, IP 54

Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).

Articles

(6 st)
  • TV090 - Regin
    TV090
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    70*72*108 mm
    Setpoint-1 value, temperature min.
    0 °C
    Setpoint-1 value, temperature max.
    90 °C
    Setpoint value, temperature range 1
    0...90 °C
    Hysteresis range 1, temperature
    4±1 K
    Breaking capacity range 1
    NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
  • TV090U - Regin
    TV090U
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    70*72*108 mm
    Setpoint-1 value, temperature min.
    0 °C
    Setpoint-1 value, temperature max.
    90 °C
    Setpoint value, temperature range 1
    0...90 °C
    Hysteresis range 1, temperature
    4±1 K
    Breaking capacity range 1
    NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
  • TV09090U - Regin
    TV09090U
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    88*70*132 mm
    Setpoint-1 value, temperature min.
    0 °C
    Setpoint-1 value, temperature max.
    90 °C
    Setpoint value, temperature range 1
    0...90 °C
    Setpoint-2 value, temperature min.
    0 °C
    Setpoint-2 value, temperature max.
    90 °C
    Setpoint value, temperature range 2
    0...90 °C
    Hysteresis range 1, temperature
    4±1 K
    Hysteresis range 2, temperature
    4±1 K
    Breaking capacity range 1
    NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
  • TVR6585 - Regin
    TVR6585
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    125 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    70*72*108 mm
    Setpoint-1 value, temperature min.
    65 °C
    Setpoint-1 value, temperature max.
    85 °C
    Setpoint value, temperature range 1
    65...85 °C
    Hysteresis range 1, temperature
    20±5 K
    Breaking capacity range 1
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
  • TVR90110 - Regin
    TVR90110
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    125 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    70*72*108 mm
    Setpoint-1 value, temperature min.
    90 °C
    Setpoint-1 value, temperature max.
    110 °C
    Setpoint value, temperature range 1
    90...110 °C
    Hysteresis range 1, temperature
    20±5 K
    Breaking capacity range 1
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
  • TV090UR110 - Regin
    TV090UR110
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    88*70*132 mm
    Setpoint-1 value, temperature min.
    90 °C
    Setpoint-1 value, temperature max.
    110 °C
    Setpoint value, temperature range 1
    90...110 °C
    Setpoint-2 value, temperature min.
    0 °C
    Setpoint-2 value, temperature max.
    90 °C
    Setpoint value, temperature range 2
    0...90 °C
    Hysteresis range 1, temperature
    20±5 K
    Hysteresis range 2, temperature
    4±1 K
    Breaking capacity range 1
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC

Specifications

Specifications for Immersion thermostats, IP 54
Appliance class Class I
Protection class IP54
Ambient humidity (non-condensing) 10…90 % RH
Ambient temp -20…65 °C
Storage temp -20…70 °C
Storage humidity 10...95 % RH
Weight, incl. packaging 0.44 kg
Material, cover ABS
Material, base PC+ABS blend (Bayblend®)

Accessories