Immersion thermostats, IP 54

Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).

Articles

(7 st)
  • TV090 - Regin
    TV090
    Temperature range 1
    0...90 °C
    Temperature range 2
    Hysteresis range 1
    4±1 K
    Hysteresis range 2
    -
    Step diff.
    Max. bulb temperature
    120 °C
    Function
    with SPDT contact
    Hidden setpoint
    -
  • TV090U - Regin
    TV090U
    Temperature range 1
    0...90 °C
    Temperature range 2
    Hysteresis range 1
    4±1 K
    Hysteresis range 2
    -
    Step diff.
    Max. bulb temperature
    120 °C
    Function
    with SPDT contact
    Hidden setpoint
    X
  • TV09090U - Regin
    TV09090U
    Temperature range 1
    0…90 °C
    Temperature range 2
    0…90 °C
    Hysteresis range 1
    4±1 K
    Hysteresis range 2
    4±1 K
    Step diff.
    Max. bulb temperature
    120 °C
    Function
    with SPDT contact
    Hidden setpoint
    X
  • TVR6585 - Regin
    TVR6585
    Temperature range 1
    65…85 °C
    Temperature range 2
    Hysteresis range 1
    20±5 K
    Hysteresis range 2
    -
    Step diff.
    Max. bulb temperature
    125 °C
    Function
    manual maximum reset
    Hidden setpoint
    -
  • TVR90110 - Regin
    TVR90110
    Temperature range 1
    90…110 °C
    Temperature range 2
    Hysteresis range 1
    20±5 K
    Hysteresis range 2
    -
    Step diff.
    Max. bulb temperature
    125 °C
    Function
    Manual maximum reset
    Hidden setpoint
    -
  • TV090UR85 - Regin
    TV090UR85
    Temperature range 1
    0…90 °C
    Temperature range 2
    65…85 °C
    Hysteresis range 1
    4±1 K
    Hysteresis range 2
    20±5 K
    Step diff.
    Max. bulb temperature
    120 °C
    Function
    manual maximum reset with SPDT contact
    Hidden setpoint
    -
  • TV090UR110 - Regin
Specifications for Immersion thermostats, IP 54
Sensor element Copper bulb with 120 mm brass pocket
Contacts Microswitches with SPDT contacts (heat/cool)
Switch capacity With SPDT contact: NC 250 V AC 16 (6) A /NO 250 V AC 6 (4) manual maximum reset: NC 250 V AC 16 (2,5) A / NO 250 V AC 0,5 A
Ambient temperature -35…+65°C
Ambient humidity 10...90 % RH (non-condensing)
Storage temperature -20…+70°C
Storage humidity < 95% RH
Casing Bayblend® base, ABS cover (2 stage models: sealed ABS)
Weight single stage: 440 g double range: 560 g
Dimensions 108 x 70 x 72mm
Protection class IP54
Isolation class I

Product sheet

Instructions

Other documentation

DBZ-30/14

Brass pocket 120 mm, ø external 8 mm, ø internal 7 mm, connection R 1/2"

DBZ-31/14

Stainless steel pocket AISI 304, 120 mm, ø external 9 mm, ø internal 7 mm, connection R 1/2"

DBZ-40/14

Brass pocket 108 mm, Ø external 16 mm, Ø internal 15 mm, connection R 1/2”

DBZ-41/14

Stainless steel pocket AISI 304 pocket, 120 mm, Ø external 16 mm, Ø internal 15 mm, connection R 1/2”