Industrietechnik

DB-TA-3B5-10A Room controllers for 2 pipe system with economy function and remote season changeover

Temperature control in heating, ventilation, refrigeration and air conditioning for typical 2-pipe fan-coil systems with proportional valve.

Specifications

Specifications for DB-TA-3B5-10A
On/off button Yes
3 speeds No
Change-over function, season Remote contact
Specifications for Room controllers for 2 pipe system with economy function and remote season changeover
Supply voltage 24 V AC ± 10%, 50/60 Hz
Input External contact for economy and season changeover function
Output Valves: 1 0-10 V outputs (R L > 10 kOhm) / speeds: 6 A 24/230 V AC, 50/60 Hz
Power consumption 1 W
Sensor NTC 10K
Ambient temperature 0…40°C
Ambient humidity 10…90 % RH (non-condensing)
Setpoint 5…30°C
Storage temperature -20…+70°C
Storage humidity < 95% RH
Economy Economy setpoint: adjustable range between 5…30°C
P-band 1...5 K
Temperature resolution 0.1°C
Casing ABS fireproof according to UL94 V-0 color (RAL 9010)
Weight 220 g
Dimensions 144 x 82 x 34mm
Protection class IP30
Isolation class II