Navigate on this page
Specifications
Supply voltage | 3-phase, 210...255 / 380...415 V AC, automatic adaptation |
---|---|
Setpoint | 0…30°C |
Max. load | Max. 25 A, min. 3 A/phase |
Sensor inputs | Two, main and min./max. limiting sensors (NTC sensor) |
Control signal | 0...10 V DC (external signal) |
Mounting | Wall |
Protection class | IP30 |
P-band | Supply air temperature control: 20 K, fixed Room temperature control: 1.5 K, fixed |
I-time (supply air temperature control) | 6 min, fixed |
Pulse period | 6...120 |
Dimensions | 160 x 207 x 94mm |