DMD-CDifferential pressure transmitter
- Power Supply
- 24VAC/DC (21...27 V AC 50/60Hz / 21...27 V DC), 5.0 VA
- Dimensions, external (WxHxD)
- 89x129x58 mm
- Display
- Yes
- Display type
- LED, three digits
- Analogue output load impedance 0...10v
- > 2 kΩ
- Analogue output load impedance 4...20mA
- < 500 Ω
- Pressure, range sensor
- 0…999 Pa
- Accuracy, pressure sensor 1
- ±1 % full scale at 20 °C %
- Measuring range pressure
- 0...100 / 0...300 / 0...500 / 0...999 Pa
- Damping (electronic)
- 0...20 s
- P-band
- 0...300 %
- I-time
- 0…999 s
- D-factor
- 0...999
Specifications
Protection class | IP54 |
---|---|
Ambient humidity (non-condensing) | 0…90 % RH |
Storage temperature | -40…50 °C |
Mounting | Wall |
Weight, incl. packaging | 0.39 kg |
Media | Air and non-corrosive gases |
Analogue outputs type (AO) | 0…10 V DC / 4…20 mA pressure Controller output signal 0...10 V DC |
Cable gland | M16x1,5 |
Terminal type | Screw Terminal |
Terminal wire size | 1.5 mm² |
Material, housing | Polycarbonate (PC) |
Material sensor | Silicone rubber |
Software & documentation
Product sheet
Instructions
Other documentation
Accessories
ANS-20
2 m plastic tube and two pressure outlets (straight)