Specifications
Temperature range | -10…+85 °C |
---|---|
Hysteresis | 0.5…6 K |
Supply voltage | 230 V AC ± 10%, 50/60 Hz |
---|---|
Input | 2 NTC 10K sensor (thermostats are supplied with NT0420 + NTC10-02) |
Output | 1 SPDT relay 10 A 230 V AC |
Power consumption | < 1.5 W |
Accuracy | ± 1 °C |
Ambient temperature | -20...+50°C |
Ambient humidity | 10…90 % RH (non-condensing) |
Setpoint | 1…20 Delta T°C |
Storage temperature | -20…+70°C |
Storage humidity | < 95% RH |
Max. temperature sensor | -40…+110°C |
Casing | ABS fireproof according to UL94 V-0 |
Weight | 580 g |
Dimensions | 132 x 85 x 88mm |
Protection class | IP65 |
Isolation class | II |