Navigate on this page
Articles
(8 st)-
NT0420-NTC1.8
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NTC1.8
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 1800 Ω at 25°C, Beta 3416
- Equivalent
- TAC
-
NT0420-NTC2.2
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NTC2.2
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 2252 Ω at 25°C, Beta 3977
- Equivalent
- Johnson Controls
-
NT0420-NTC10-01
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NTC10-01
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 10 kΩ at 25°C, Beta 3977
- Equivalent
- Aquatrol, Johnson Controls, Satchwell, Trend, Cylon, Honeywell
-
NT0420-NTC10-02
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NTC10-02
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 10 kΩ at 25°C, Beta 3435
- Equivalent
- Carel, Evco, Eliwell, AB Industrietechnik
-
NT0420-NTC10-03
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NTC10-03
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 10 kΩ at 25°C, Beta 3695
- Equivalent
- Andover, Delta Controls, Siebe, York
-
NT0420-NTC20
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NTC20
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 20 kΩ at 25°C, Beta 4262
- Equivalent
- Honeywell
-
NT0420-NI1000-01
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NI1000-01
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 1000 Ω at 0°C, TCR 5000
- Equivalent
- Siemens, Landis & Staefa
-
NT0420-NI1000-02
- Mounting
- Bulb
- Cable length
- 2 m
- Element type
- NI1000-02
- Measuring range, temp
- -50…110 °C
- Nominal resistance
- 1000 Ω at 0°C, TCR 6180
- Equivalent
- Sauter
Specifications
Protection class | IP67 |
---|---|
Bulb length | 40 mm |
Bulb diameter | 4 mm |
Material cable | TPE |
Material sensor | Stainless steel AISI 304 |