Industrietechnik

Room sensor with setpoint adjustment

For room temperature measurement. Can also be used solely for setpoint adjustment.

Articles

(11 st)
  • SAP-PT100-2 - Regin
    SAP-PT100-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    PT100
    Measuring range, temp
    0…50 °C
    Sensor element, class
    DIN Class B: ±(0.3 + .005 |T|°C)
    Nominal resistance
    100 Ω at 0°C
    Setpoint range
    5…30 °C
  • SAP-PT1000-1 - Regin
    SAP-PT1000-1
    Room sensor with setpoint adjustment
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    PT1000
    Measuring range, temp
    0…50 °C
    Sensor element, class
    DIN Class B: ±(0.3 + .005 |T|°C)
    Nominal resistance
    1000 Ω at 0°C
    Setpoint range
    5…31 °C
  • SAP-PT1000-2 - Regin
    SAP-PT1000-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    PT1000
    Measuring range, temp
    0…50 °C
    Sensor element, class
    DIN Class B: ±(0.3 + .005 |T|°C)
    Nominal resistance
    1000 Ω at 0°C
    Setpoint range
    5…30 °C
  • SAP-NTC1.8-2 - Regin
    SAP-NTC1.8-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NTC1.8
    Measuring range, temp
    0…50 °C
    Nominal resistance
    1800 Ω at 25°C, Beta 3416
    Setpoint range
    5…30 °C
    Equivalent
    TAC
  • SAP-NTC2.2-2 - Regin
    SAP-NTC2.2-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NTC2.2
    Measuring range, temp
    0…50 °C
    Nominal resistance
    2252 Ω at 25°C, Beta 3977
    Setpoint range
    5…30 °C
    Equivalent
    TAC
  • SAP-NTC10-02-2 - Regin
    SAP-NTC10-02-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NTC10-02
    Measuring range, temp
    0…50 °C
    Nominal resistance
    10 kΩ at 25°C, Beta 3435
    Setpoint range
    5…30 °C
    Equivalent
    Carel - Evco - Eliwell - AB Industrietechnik
  • SAP-NTC10-03-2 - Regin
    SAP-NTC10-03-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NTC10-03
    Measuring range, temp
    0…50 °C
    Nominal resistance
    10 kΩ at 25°C, Beta 3695
    Setpoint range
    5…30 °C
    Equivalent
    Andover - Delta Controls - Siebe - York
  • SAP-NTC15-01-3 - Regin
    SAP-NTC15-01-3
    Room sensor
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NTC15
    Measuring range, temp
    0…30 °C
    Nominal resistance
    15 kΩ at 0°C
    Setpoint range
    5…30 °C
    Equivalent
    Regin - AB Industrietechnik
  • SAP-NTC20-2 - Regin
    SAP-NTC20-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NTC20
    Measuring range, temp
    0…50 °C
    Nominal resistance
    20 kΩ at 25°C, Beta 4262
    Setpoint range
    5…30 °C
    Equivalent
    Honeywell
  • SAP-NI1000-01-2 - Regin
    SAP-NI1000-01-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NI1000-01
    Measuring range, temp
    0…50 °C
    Nominal resistance
    1000 Ω at 0°C, TK5000
    Setpoint range
    5…30 °C
    Equivalent
    Siemens - Landis & Staefa
  • SAP-NI1000-02-2 - Regin
    SAP-NI1000-02-2
    Mounting
    Room
    Dimensions, external (WxHxD)
    86x86x30 mm
    Element type
    NI1000-02
    Measuring range, temp
    0…50 °C
    Nominal resistance
    1000 Ω at 0°C, TK6180
    Setpoint range
    5…30 °C
    Equivalent
    Sauter

Specifications

Specifications for Room sensor with setpoint adjustment
Protection class IP30
Mounting Wall
Terminal type Screw Terminal
Terminal wire size 1.5 mm²