Industrietechnik

Immersion thermostats, IP 54

Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).

Articles

(6 st)
  • TV090 - Regin
    TV090
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Switching capacity
    NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
    Setpoint value, temperature range
    0...90 °C
    Hysteresis, temperature
    4±1 K
    Dimensions, external (WxHxD)
    70x72x108 mm
    Measurand
    Temperature
    Medium
    Liquid
    Mounting
    Immersion
    Reset function
    Automatic
    Pipe fitting
    Male threaded
    Conformity
    CE
  • TV090U - Regin
    TV090U
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Switching capacity
    NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
    Setpoint value, temperature range
    0...90 °C
    Hysteresis, temperature
    4±1 K
    Dimensions, external (WxHxD)
    70x72x108 mm
    Measurand
    Temperature
    Medium
    Liquid
    Mounting
    Immersion
    Reset function
    Automatic
    Pipe fitting
    Male threaded
    Conformity
    CE
  • TV09090U - Regin
    TV09090U
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    88x70x132 mm
    Setpoint-1 value, temperature min.
    0 °C
    Setpoint-1 value, temperature max.
    90 °C
    Setpoint value, temperature range 1
    0...90 °C
    Setpoint-2 value, temperature min.
    0 °C
    Setpoint-2 value, temperature max.
    90 °C
    Setpoint value, temperature range 2
    0...90 °C
    Hysteresis range 1, temperature
    4±1 K
    Hysteresis range 2, temperature
    4±1 K
    Breaking capacity range 1
    NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC
    Measurand
    Temperature
    Medium
    Liquid
    Mounting
    Immersion
    Reset function
    Automatic
    Pipe fitting
    Male threaded
    Conformity
    CE
  • TVR6585 - Regin
    TVR6585
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    125 °C
    Electrical contact
    SPDT microswitch
    Switching capacity
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
    Setpoint value, temperature range
    65...85 °C
    Hysteresis, temperature
    20±5 K
    Dimensions, external (WxHxD)
    70x72x108 mm
    Measurand
    Temperature
    Medium
    Liquid
    Mounting
    Immersion
    Reset function
    Manual
    Pipe fitting
    Male threaded
    Conformity
    CE
  • TVR90110 - Regin
    TVR90110
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    125 °C
    Electrical contact
    SPDT microswitch
    Switching capacity
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
    Setpoint value, temperature range
    90...110 °C
    Hysteresis, temperature
    20±5 K
    Dimensions, external (WxHxD)
    70x72x108 mm
    Breaking capacity range 1
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
    Measurand
    Temperature
    Medium
    Liquid
    Mounting
    Immersion
    Reset function
    Manual
    Pipe fitting
    Male threaded
    Conformity
    CE
  • TV090UR110 - Regin
    TV090UR110
    Sensor element
    Liquid-filled copper capillary with 120 mm brass pocket
    Max. probe temperature
    120 °C
    Electrical contact
    SPDT microswitch
    Dimensions, external (WxHxD)
    88x70x132 mm
    Setpoint-1 value, temperature min.
    90 °C
    Setpoint-1 value, temperature max.
    110 °C
    Setpoint value, temperature range 1
    90...110 °C
    Setpoint-2 value, temperature min.
    0 °C
    Setpoint-2 value, temperature max.
    90 °C
    Setpoint value, temperature range 2
    0...90 °C
    Hysteresis range 1, temperature
    20±5 K
    Hysteresis range 2, temperature
    4±1 K
    Breaking capacity range 1
    NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
    Measurand
    Temperature
    Medium
    Liquid
    Mounting
    Immersion
    Reset function
    Manual
    Pipe fitting
    Male threaded
    Conformity
    CE

Specifications

Specifications for Immersion thermostats, IP 54
Appliance class Class I
Protection class IP54
Ambient humidity (non-condensing) 10…90 % RH
Storage temperature -20…70 °C
Storage humidity 10...95 % RH
Weight, incl. packaging 0.44 kg
Material, cover ABS
Material, base PC+ABS blend (Bayblend®)

Accessories