Industrietechnik
TV090UR110 Immersion thermostats, IP 54
Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).
Navigate on this page
Specifications
Sensor element | Liquid-filled copper capillary with 120 mm brass pocket |
---|---|
Electrical contact | SPDT microswitch |
Dimensions, external (WxHxD) | 88x70x132 mm |
Setpoint value, temperature range 1 | 90...110 °C |
Setpoint value, temperature range 2 | 0...90 °C |
Hysteresis range 1, temperature | 20±5 K |
Hysteresis range 2, temperature | 4±1 K |
Breaking capacity range 1 | NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC |
Breaking capacity range 2 | NC 16 (6) A, 250 V AC / NO 6 (4) A, 250 V AC |
Measurand | Temperature |
Medium | Liquid |
Mounting | Immersion |
Reset function | Manual |
Pipe fitting | Male threaded |
Conformity | CE |
Max. probe temperature | 120 °C |
---|---|
Appliance class | Class I |
Protection class | IP54 |
Ambient humidity (non-condensing) | 10…90 % RH |
Storage temperature | -20…70 °C |
Storage humidity | 10...95 % RH |
Weight, incl. packaging | 0.44 kg |
Material, cover | ABS |
Material, base | PC+ABS blend (Bayblend®) |
Software & documentation
Accessories
DBZ-30/14
Brass pocket 120 mm, ø external 8 mm, ø internal 7 mm, connection R 1/2"
DBZ-40/14
Brass pocket 108 mm, Ø external 16 mm, Ø internal 15 mm, connection R 1/2”
DBZ-31/14
Stainless steel pocket AISI 304, 120 mm, ø external 9 mm, ø internal 7 mm, connection R 1/2"
DBZ-41/14
Stainless steel pocket AISI 304 pocket, 120 mm, Ø external 16 mm, Ø internal 15 mm, connection R 1/2”