Industrietechnik

TVR90110 Immersion thermostats, IP 54

Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).

Specifications

Specifications for TVR90110
Sensor element Liquid-filled copper capillary with 120 mm brass pocket
Max. probe temperature 125 °C
Electrical contact SPDT microswitch
Switching capacity NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
Setpoint value, temperature range 90...110 °C
Hysteresis, temperature 20±5 K
Dimensions, external (WxHxD) 70x72x108 mm
Breaking capacity range 1 NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
Measurand Temperature
Medium Liquid
Mounting Immersion
Reset function Manual
Pipe fitting Male threaded
Conformity CE
Specifications for Immersion thermostats, IP 54
Appliance class Class I
Protection class IP54
Ambient humidity (non-condensing) 10…90 % RH
Storage temperature -20…70 °C
Storage humidity 10...95 % RH
Weight, incl. packaging 0.44 kg
Material, cover ABS
Material, base PC+ABS blend (Bayblend®)

Accessories