Specifications for TVR90110
Sensor element Liquid-filled copper capillary with 120 mm brass pocket
Electrical contact SPDT microswitch
Switching capacity NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
Setpoint value, temperature range 90...110 °C
Hysteresis, temperature 20±5 K
Dimensions, external (WxHxD) 70x72x108 mm
Breaking capacity range 1 NC 16 (2.5) A, 250 V AC / NO 0.5 A, 250 V AC
Measurand Temperature
Medium Liquid
Mounting Immersion
Reset function Manual
Pipe fitting Male threaded
Conformity CE
Specifications for Immersion thermostats, IP 54
Max. probe temperature 120 °C
Appliance class Class I
Protection class IP54
Ambient humidity (non-condensing) 10…90 % RH
Storage temperature -20…70 °C
Storage humidity 10...95 % RH
Weight, incl. packaging 0.44 kg
Material, cover ABS
Material, base PC+ABS blend (Bayblend®)

Accessories