Industrietechnik
Differential pressure transmitters
Differential pressure transmitter for monitoring differential gaseous pressure, non-aggressive media. Can be mounted in any position.
Possible areas of applications are:
- air-conditioning and clean rooms;
- building automation;
- valve and flap control;
- fluid and level monitoring;
- control of air flows.
Navigate on this page
Articles
(7 st)-
984M.323204
- Mounting
- Wall
- Power Supply
- 24VDC (18...30 V DC)
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Analogue output load impedance 4...20mA
- 20…500 Ω
- Response time
- 200 ms or 1 s, selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- 0...100 Pa / 0...250 Pa
- Max. allowed diff. Pressure sensor 1
- 60 kPa
-
984M.343304
- Power Supply
- 24VAC/DC (18...30 V AC 50Hz / 18...30 V DC), 6.0 VA
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Analogue output load impedance 4...20mA
- 20…500 Ω
- Response time
- 100 ms or 1 sec., selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- 0...500 Pa / 0...1000 Pa
- Max. allowed diff. Pressure sensor 1
- 75 kPa
-
984M.343714
- Power Supply
- 24VAC/DC (18...30 V AC 50Hz / 18...30 V DC), 6.0 VA
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Display
- Yes
- Display type
- LED, 4 digits
- Analogue output load impedance 0...10v
- ≤ 10mA
- Response time
- 100 ms or 1 sec., selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- 0...500 Pa / 0...1000 Pa
- Max. allowed diff. Pressure sensor 1
- 75 kPa
-
984M.353704
- Power Supply
- 24VAC/DC (18...30 V AC 50Hz / 18...30 V DC), 6.0 VA
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Analogue output load impedance 0...10v
- ≤ 10mA
- Response time
- 100 ms or 1 sec., selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- 0...1 kPa / 0...2.5 kPa
- Max. allowed diff. Pressure sensor 1
- 85 kPa
-
984M.353D04
- Power Supply
- 24VAC/DC (18...30 V AC 50Hz / 18...30 V DC), 6.0 VA
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Analogue output load impedance 4...20mA
- 20...500 Ω
- Response time
- 100 ms or 1 sec., selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- 0...1 kPa / 0...2.5 kPa
- Max. allowed diff. Pressure sensor 1
- 85 kPa
-
984M.3x3204
- Power Supply
- 24VAC/DC (18...30 V AC 50Hz / 18...30 V DC), 6.0 VA
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Analogue output load impedance 4...20mA
- 20…500 Ω
- Response time
- 100 ms or 1 sec., selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- -50...+50 Pa
- Max. allowed diff. Pressure sensor 1
- 60 kPa
-
984M.3x3114
- Power Supply
- 24VAC/DC (18...30 V AC 50Hz / 18...30 V DC), 6.0 VA
- Dimensions, external (WxHxD)
- 85x100x58 mm
- Display
- Yes
- Display type
- LED, 4 digits
- Analogue output load impedance 0...10v
- ≤ 10mA
- Response time
- 100 ms or 1 sec., selectable
- Accuracy, pressure sensor 1
- <±2 % full scale %
- Measuring range pressure
- -50...+50 Pa
- Max. allowed diff. Pressure sensor 1
- 60 kPa
Specifications
Protection class | IP54 |
---|---|
Ambient humidity (non-condensing) | 0…95 % RH |
Storage temperature | -20…70 °C |
Mounting | Wall |
Weight, incl. packaging | 0.14 kg |
Media | Air and non-corrosive gases |
Cable gland | M20x1,5 |
Terminal type | Screw Terminal |
Terminal wire size | 1.5 mm² |
Material, housing | ABS |
Material, base | POM |