Industrietechnik

TUTC1102 Duct humidity/temperature transmitter

Specifications

Specifications for TUTC1102
Mounting Duct
Dimensions, external (WxHxD) 75x103x266 mm
Tube length 23 cm
Tube diameter 12 mm
Insertion length 60…230 mm
Analogue output load impedance 4...20mA With power supply 11...17 V DC: RL <50 Ω
Relay With power supply 21...30 V DC: RL < 500 Ω
Measuring range, temp -20…50 °C
Output temperature NTC 10K-02 B3435
Measuring range, humidity 0…100 % RH
Output humidity 4-20 mA (2 wire)
Hysteresis, humidity ± 3% RH
Accuracy, gas in air 0.6
Colour, cover White
Colour, base White
Power supply (4...20 mA) Max 30 V DC, Min 11+(0.02xRL) V DC
Power consumption < 1 W
Specifications for Duct humidity/temperature transmitter
Appliance class Class III
Protection class IP65
Ambient humidity (non-condensing) 10…95 % RH
Storage temperature -20…70 °C
Mounting Duct
Weight, incl. packaging 0.26 kg
Accuracy, temperature 1 K
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 0.75 mm²
Material, housing Polycarbonate

Accessories