VFBV2/VFBV3 - 2- and 3-way ball valves
Ball valves, DN15-50, kvs 0.6-63, designed for control of hot, cold or glycol-mixed water in heating and ventilation systems. These ball valves can be used as either characterized control ball valves when a flow plate is installed in port A (default mode), or as on/off ball valves when the flow plate is removed. When the flow plate is removed the Kvs between port A and AB is increased. To be coupled to SEB4 / SEB5 actuators.
Navigate on this page
Articles
(12 st)-
VFBV215
- Nominal diameter
- DN15
- Kvs with flow plate installed in port A
- 0.6/1.0/1.6/2.5/4.0 m 3 /h
- Kvs (On/off, A-AB)
- 6.3 m 3 /h
- Actuator
- SEB4
- ΔPs
- 2500 kPa
- ΔPmax
- 350 kPa
-
VFBV220
- Nominal diameter
- DN20
- Kvs with flow plate installed in port A
- 6.3 m 3 /h
- Kvs (On/off, A-AB)
- 10 m 3 /h
- Actuator
- SEB4
- ΔPs
- 2500 kPa
- ΔPmax
- 350 kPa
-
VFBV225
- Nominal diameter
- DN25
- Kvs with flow plate installed in port A
- 10 m 3 /h
- Kvs (On/off, A-AB)
- 16 m 3 /h
- Actuator
- SEB4
- ΔPs
- 2500 kPa
- ΔPmax
- 350 kPa
-
VFBV232
- Nominal diameter
- DN32
- Kvs with flow plate installed in port A
- 16 m 3 /h
- Kvs (On/off, A-AB)
- 25 m 3 /h
- Actuator
- SEB5
- ΔPs
- 1600 kPa
- ΔPmax
- 350 kPa
-
VFBV240
- Nominal diameter
- DN40
- Kvs with flow plate installed in port A
- 25 m 3 /h
- Kvs (On/off, A-AB)
- 40 m 3 /h
- Actuator
- SEB5
- ΔPs
- 1600 kPa
- ΔPmax
- 350 kPa
-
VFBV250
- Nominal diameter
- DN50
- Kvs with flow plate installed in port A
- 40 m 3 /h
- Kvs (On/off, A-AB)
- 63 m 3 /h
- Actuator
- SEB5
- ΔPs
- 1600 kPa
- ΔPmax
- 350 kPa
-
VFBV315
- Nominal diameter
- DN15
- Kvs with flow plate installed in port A
- 0.6/1.0/1.6/2.5/4.0 m 3 /h
- Kvs (On/off, A-AB)
- 6.3 m 3 /h
- Kvs (On/off, B-AB)
- 4 m 3 /h
- Actuator
- SEB4
- ΔPs
- 2500 kPa
- ΔPmax
- 350 kPa
-
VFBV320
- Nominal diameter
- DN20
- Kvs with flow plate installed in port A
- 6.3 m 3 /h
- Kvs (On/off, A-AB)
- 10 m 3 /h
- Kvs (On/off, B-AB)
- 6.3 m 3 /h
- Actuator
- SEB4
- ΔPs
- 2500 kPa
- ΔPmax
- 350 kPa
-
VFBV325
- Nominal diameter
- DN25
- Kvs with flow plate installed in port A
- 10 m 3 /h
- Kvs (On/off, A-AB)
- 16 m 3 /h
- Kvs (On/off, B-AB)
- 10 m 3 /h
- Actuator
- SEB4
- ΔPs
- 2500 kPa
- ΔPmax
- 350 kPa
-
VFBV332
- Nominal diameter
- DN32
- Kvs with flow plate installed in port A
- 16 m 3 /h
- Kvs (On/off, A-AB)
- 25 m 3 /h
- Kvs (On/off, B-AB)
- 16 m 3 /h
- Actuator
- SEB5
- ΔPs
- 1600 kPa
- ΔPmax
- 350 kPa
-
VFBV340
- Nominal diameter
- DN40
- Kvs with flow plate installed in port A
- 25 m 3 /h
- Kvs (On/off, A-AB)
- 40 m 3 /h
- Kvs (On/off, B-AB)
- 25 m 3 /h
- Actuator
- SEB5
- ΔPs
- 1600 kPa
- ΔPmax
- 350 kPa
-
VFBV350
- Nominal diameter
- DN50
- Kvs with flow plate installed in port A
- 40 m 3 /h
- Kvs (On/off, A-AB)
- 63 m 3 /h
- Kvs (On/off, B-AB)
- 40 m 3 /h
- Actuator
- SEB5
- ΔPs
- 1600 kPa
- ΔPmax
- 350 kPa
Specifications
Application | Heating systems, cooling systems, ventilation systems |
---|---|
Pressure rating | PN40 |
Connection | BSP internally threaded according to ISO 228/1 |
Flow characteristics | A - AB = equal percentage (Flow plate installed), B - AB = linear, On/Off (No flow plate) |
Max. leakage | 0.0 % of the kvs value |
Media | Hot water, cold water, glycol-mixed water |
Media temperature | -5…+140°C |
Rangeability | 100:1 |
Body | Brass CW617N |
Ball | Chromed brass CW614N |
Seat | PTFE |
Stem | Stainless steel 1.4305 |
Flow plate | POM |
Circlips | Stainless steel 1.4310 |
O-rings | EPDM |
Accessories

VF-HL1
Hand lever for manual operation of ball valves