Industrietechnik

Differential pressure transmitter for liquids and gases

Differential pressure transmitter for measurement of liquids (also glycol-mixed) and gases (not ammonia).

Articles

(20 st)
  • TPDL10 - Regin
    TPDL10
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...10 kPa
    Max. overload pressure
    60 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Accuracy, long-term stability according to IEC EN 60770-1
    ±0.5 %
    Resolution
    0.25 fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL10-420 - Regin
    TPDL10-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...10 kPa
    Max. overload pressure
    60 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL20 - Regin
    TPDL20
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...20 kPa
    Max. overload pressure
    120 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL20-420 - Regin
    TPDL20-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...20 kPa
    Max. overload pressure
    120 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL40 - Regin
    TPDL40
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...40 kPa
    Max. overload pressure
    200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL40-420 - Regin
    TPDL40-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...40 kPa
    Max. overload pressure
    200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL100 - Regin
    TPDL100
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...100 kPa
    Max. overload pressure
    500 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL100-420 - Regin
    TPDL100-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...100 kPa
    Max. overload pressure
    500 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL250 - Regin
    TPDL250
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...250 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL250-420 - Regin
    TPDL250-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...250 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL400 - Regin
    TPDL400
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...400 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.75 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL400-420 - Regin
    TPDL400-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...400 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL600 - Regin
    TPDL600
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...600 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.4 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL600-420 - Regin
    TPDL600-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...600 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL1000 - Regin
    TPDL1000
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...1000 kPa
    Max. overload pressure
    2000 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.4 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL1000-420 - Regin
    TPDL1000-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...1000 kPa
    Max. overload pressure
    2000 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL1600 - Regin
    TPDL1600
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...1600 kPa
    Max. overload pressure
    3200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.4 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL1600-420 - Regin
    TPDL1600-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...1600 kPa
    Max. overload pressure
    3200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m
  • TPDL2500 - Regin
    TPDL2500
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0...2500 kPa
    Max. overload pressure
    5000 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.4 % fs %
    Cabel
    Three wire cable, 1.5 m
  • TPDL2500-420 - Regin
    TPDL2500-420
    Dimensions, external (WxHxD)
    40*79* mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0...2500 kPa
    Max. overload pressure
    5000 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs %
    Cabel
    Two wire cable, 1.5 m

Specifications

Specifications for Differential pressure transmitter for liquids and gases
Power Supply 18…33 V DC / 24 V AC ±15%, 0,1 VA
Protection class IP65
Ambient temp -15…85 °C
Storage temp -15…85 °C
Media liquids and gases
Pressure connection 6 mm for copper tube
Dynamic response time <5 ms
Material, housing Stainless steel 1.4305
Material sensor Ceramic material

Accessories