Industrietechnik

VFBV2/VFBV3 - 2- and 3-way ball valves

Ball valves, DN15-50, kvs 0.6-63, designed for control of hot, cold or glycol-mixed water in heating and ventilation systems. These ball valves can be used as either characterized control ball valves when a flow plate is installed in port A (default mode), or as on/off ball valves when the flow plate is removed. When the flow plate is removed the Kvs between port A and AB is increased. To be coupled to SEB4 / SEB5 actuators.

Articles

(12 st)
  • VFBV215 - Regin
    VFBV215
    Nominal diameter
    DN15
    Kvs with flow plate installed in port A
    0.6/1.0/1.6/2.5/4.0 m 3 /h
    Kvs (On/off, A-AB)
    6.3 m 3 /h
    Actuator
    SEB4
    ΔPs
    2500 kPa
    ΔPmax
    350 kPa
  • VFBV220 - Regin
    VFBV220
    Nominal diameter
    DN20
    Kvs with flow plate installed in port A
    6.3 m 3 /h
    Kvs (On/off, A-AB)
    10 m 3 /h
    Actuator
    SEB4
    ΔPs
    2500 kPa
    ΔPmax
    350 kPa
  • VFBV225 - Regin
    VFBV225
    Nominal diameter
    DN25
    Kvs with flow plate installed in port A
    10 m 3 /h
    Kvs (On/off, A-AB)
    16 m 3 /h
    Actuator
    SEB4
    ΔPs
    2500 kPa
    ΔPmax
    350 kPa
  • VFBV232 - Regin
    VFBV232
    Nominal diameter
    DN32
    Kvs with flow plate installed in port A
    16 m 3 /h
    Kvs (On/off, A-AB)
    25 m 3 /h
    Actuator
    SEB5
    ΔPs
    1600 kPa
    ΔPmax
    350 kPa
  • VFBV240 - Regin
    VFBV240
    Nominal diameter
    DN40
    Kvs with flow plate installed in port A
    25 m 3 /h
    Kvs (On/off, A-AB)
    40 m 3 /h
    Actuator
    SEB5
    ΔPs
    1600 kPa
    ΔPmax
    350 kPa
  • VFBV250 - Regin
    VFBV250
    Nominal diameter
    DN50
    Kvs with flow plate installed in port A
    40 m 3 /h
    Kvs (On/off, A-AB)
    63 m 3 /h
    Actuator
    SEB5
    ΔPs
    1600 kPa
    ΔPmax
    350 kPa
  • VFBV315 - Regin
    VFBV315
    Nominal diameter
    DN15
    Kvs with flow plate installed in port A
    0.6/1.0/1.6/2.5/4.0 m 3 /h
    Kvs (On/off, A-AB)
    6.3 m 3 /h
    Kvs (On/off, B-AB)
    4 m 3 /h
    Actuator
    SEB4
    ΔPs
    2500 kPa
    ΔPmax
    350 kPa
  • VFBV320 - Regin
    VFBV320
    Nominal diameter
    DN20
    Kvs with flow plate installed in port A
    6.3 m 3 /h
    Kvs (On/off, A-AB)
    10 m 3 /h
    Kvs (On/off, B-AB)
    6.3 m 3 /h
    Actuator
    SEB4
    ΔPs
    2500 kPa
    ΔPmax
    350 kPa
  • VFBV325 - Regin
    VFBV325
    Nominal diameter
    DN25
    Kvs with flow plate installed in port A
    10 m 3 /h
    Kvs (On/off, A-AB)
    16 m 3 /h
    Kvs (On/off, B-AB)
    10 m 3 /h
    Actuator
    SEB4
    ΔPs
    2500 kPa
    ΔPmax
    350 kPa
  • VFBV332 - Regin
    VFBV332
    Nominal diameter
    DN32
    Kvs with flow plate installed in port A
    16 m 3 /h
    Kvs (On/off, A-AB)
    25 m 3 /h
    Kvs (On/off, B-AB)
    16 m 3 /h
    Actuator
    SEB5
    ΔPs
    1600 kPa
    ΔPmax
    350 kPa
  • VFBV340 - Regin
    VFBV340
    Nominal diameter
    DN40
    Kvs with flow plate installed in port A
    25 m 3 /h
    Kvs (On/off, A-AB)
    40 m 3 /h
    Kvs (On/off, B-AB)
    25 m 3 /h
    Actuator
    SEB5
    ΔPs
    1600 kPa
    ΔPmax
    350 kPa
  • VFBV350 - Regin
    VFBV350
    Nominal diameter
    DN50
    Kvs with flow plate installed in port A
    40 m 3 /h
    Kvs (On/off, A-AB)
    63 m 3 /h
    Kvs (On/off, B-AB)
    40 m 3 /h
    Actuator
    SEB5
    ΔPs
    1600 kPa
    ΔPmax
    350 kPa

Specifications

Specifications for VFBV2/VFBV3 - 2- and 3-way ball valves
Application Heating systems, cooling systems, ventilation systems
Pressure rating PN40
Connection BSP internally threaded according to ISO 228/1
Flow characteristics A - AB = equal percentage (Flow plate installed), B - AB = linear, On/Off (No flow plate)
Max. leakage 0.0 % of the kvs value
Media Hot water, cold water, glycol-mixed water
Media temperature -5…+140°C
Rangeability 100:1
Body Brass CW617N
Ball Chromed brass CW614N
Seat PTFE
Stem Stainless steel 1.4305
Flow plate POM
Circlips Stainless steel 1.4310
O-rings EPDM

Accessories